Is it normal for GFCI receptacles to explode and burn?





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty{ margin-bottom:0;
}






up vote
13
down vote

favorite












I noticed my tooth brush wasn't charging one morning and none of the plugs in my bathroom were getting power, I went down to the circuit box and saw a flipped breaker so I flipped it back and it immediately tripped again. I tried it once more with the same result so I started to investigate the plugs in my house to see if anything was obviously wrong.



The external GFI on my deck had obvious signs of smoke on the siding so I disassembled the outlet and the entire back of the GFI blew out.



enter image description here



enter image description here



Is that a normal failure mode? Could it be a manufacture defect / installation issue?



There was obviously a lot of heat as the wire connectors appear scorched and the box is filled with a thick black soot.



enter image description here



Do I need to worry about additional damage to the wires beyond what is visible in the box or can I just remove the damaged wires and install a new GFI? Time to call an electrician?



Additional GFI Outlet Images










share|improve this question









New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 14




    What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
    – Tyson
    Nov 12 at 14:19






  • 4




    This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
    – Harper
    Nov 12 at 16:30








  • 29




    Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
    – Eric Lippert
    Nov 12 at 17:30






  • 4




    Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
    – Eric Lippert
    Nov 12 at 17:32






  • 9




    If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
    – Wayne Werner
    Nov 13 at 0:55

















up vote
13
down vote

favorite












I noticed my tooth brush wasn't charging one morning and none of the plugs in my bathroom were getting power, I went down to the circuit box and saw a flipped breaker so I flipped it back and it immediately tripped again. I tried it once more with the same result so I started to investigate the plugs in my house to see if anything was obviously wrong.



The external GFI on my deck had obvious signs of smoke on the siding so I disassembled the outlet and the entire back of the GFI blew out.



enter image description here



enter image description here



Is that a normal failure mode? Could it be a manufacture defect / installation issue?



There was obviously a lot of heat as the wire connectors appear scorched and the box is filled with a thick black soot.



enter image description here



Do I need to worry about additional damage to the wires beyond what is visible in the box or can I just remove the damaged wires and install a new GFI? Time to call an electrician?



Additional GFI Outlet Images










share|improve this question









New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 14




    What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
    – Tyson
    Nov 12 at 14:19






  • 4




    This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
    – Harper
    Nov 12 at 16:30








  • 29




    Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
    – Eric Lippert
    Nov 12 at 17:30






  • 4




    Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
    – Eric Lippert
    Nov 12 at 17:32






  • 9




    If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
    – Wayne Werner
    Nov 13 at 0:55













up vote
13
down vote

favorite









up vote
13
down vote

favorite











I noticed my tooth brush wasn't charging one morning and none of the plugs in my bathroom were getting power, I went down to the circuit box and saw a flipped breaker so I flipped it back and it immediately tripped again. I tried it once more with the same result so I started to investigate the plugs in my house to see if anything was obviously wrong.



The external GFI on my deck had obvious signs of smoke on the siding so I disassembled the outlet and the entire back of the GFI blew out.



enter image description here



enter image description here



Is that a normal failure mode? Could it be a manufacture defect / installation issue?



There was obviously a lot of heat as the wire connectors appear scorched and the box is filled with a thick black soot.



enter image description here



Do I need to worry about additional damage to the wires beyond what is visible in the box or can I just remove the damaged wires and install a new GFI? Time to call an electrician?



Additional GFI Outlet Images










share|improve this question









New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











I noticed my tooth brush wasn't charging one morning and none of the plugs in my bathroom were getting power, I went down to the circuit box and saw a flipped breaker so I flipped it back and it immediately tripped again. I tried it once more with the same result so I started to investigate the plugs in my house to see if anything was obviously wrong.



The external GFI on my deck had obvious signs of smoke on the siding so I disassembled the outlet and the entire back of the GFI blew out.



enter image description here



enter image description here



Is that a normal failure mode? Could it be a manufacture defect / installation issue?



There was obviously a lot of heat as the wire connectors appear scorched and the box is filled with a thick black soot.



enter image description here



Do I need to worry about additional damage to the wires beyond what is visible in the box or can I just remove the damaged wires and install a new GFI? Time to call an electrician?



Additional GFI Outlet Images







electrical gfci fire-hazard






share|improve this question









New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question









New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question








edited Nov 15 at 13:55









isherwood

43.3k453108




43.3k453108






New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked Nov 12 at 14:00









almarshall

6914




6914




New contributor




almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






almarshall is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.








  • 14




    What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
    – Tyson
    Nov 12 at 14:19






  • 4




    This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
    – Harper
    Nov 12 at 16:30








  • 29




    Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
    – Eric Lippert
    Nov 12 at 17:30






  • 4




    Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
    – Eric Lippert
    Nov 12 at 17:32






  • 9




    If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
    – Wayne Werner
    Nov 13 at 0:55














  • 14




    What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
    – Tyson
    Nov 12 at 14:19






  • 4




    This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
    – Harper
    Nov 12 at 16:30








  • 29




    Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
    – Eric Lippert
    Nov 12 at 17:30






  • 4




    Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
    – Eric Lippert
    Nov 12 at 17:32






  • 9




    If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
    – Wayne Werner
    Nov 13 at 0:55








14




14




What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
– Tyson
Nov 12 at 14:19




What type of cover did it have? My guess is water went in thru the face and saturated the circuit board inside. The wire insulation (except the crispy ends) remains intact, suggesting the fire came from within the GFCI, not the area beside or behind it.
– Tyson
Nov 12 at 14:19




4




4




This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
– Harper
Nov 12 at 16:30






This is why I don't like putting GFCIs outdoors. Did you disassemble it with the power on?
– Harper
Nov 12 at 16:30






29




29




Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
– Eric Lippert
Nov 12 at 17:30




Others have noted that the box is almost certainly not rated for outdoor use. But the thing that no one has mentioned yet that struck me as very odd is: why is your bathroom on the same circuit as your exterior outlet? Bathrooms are supposed to have a GFCI-protected circuit just for the bathroom plugs. This sounds like a good opportunity to review all the wiring in your house, because we've just seen that there are serious fire risks and code violations; there are probably more.
– Eric Lippert
Nov 12 at 17:30




4




4




Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
– Eric Lippert
Nov 12 at 17:32




Speaking of which, a common mistake I see is to put the bathroom GFCI on the same circuit as the bathroom lights, which is completely wrong. If the GFCI trips because you got water on the electric shaver plug, you don't want the lights to go out. Make sure you double-check that while you're doing your review of your electrical system.
– Eric Lippert
Nov 12 at 17:32




9




9




If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
– Wayne Werner
Nov 13 at 0:55




If you flip a breaker and it immediately flips back STOP! You shouldn't try again - the fact that it's immediately flipped means that something very, very bad is happening somewhere along that path.
– Wayne Werner
Nov 13 at 0:55










3 Answers
3






active

oldest

votes

















up vote
21
down vote













This happens all the time if an exterior GFCI is not weather-resistant. I've never had a weather resistant GFCI go up in smoke.



Yes, they can be in a metal box, but they still should be marked WR (weather resistant) - this means the electronics inside are coated to reduce the chances of moisture causing exactly what happened with your GFCI.



If it had shorted to the box, the metal screw would have arced and tripped the breaker. If it had shorted on the load side, it would have tripped the GFCI. But, in this case, enough moisture got in and the electronics shorted and let the magic smoke out.



Last item on the list is that it should have an in-use cover or an extra duty cover, that allows a cord to be plugged in with the cover protecting from rain.



In this case, replace your GFCI with a WR rated GFCI and add an in-use cover to greatly reduce the chance of this happening again. In some jurisdictions the local ordinances require the outlet itself to be GFCI so it can be reset (not running cords inside because of tripping the GFCI in wet grass with an electric mower is the "why" the inspector told me).






share|improve this answer



















  • 2




    This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
    – Eric Lippert
    Nov 12 at 17:27










  • Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
    – almarshall
    Nov 12 at 20:26










  • Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
    – Perkins
    Nov 12 at 22:26










  • @almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
    – Crowley
    Nov 12 at 22:39










  • As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
    – Ed Beal
    Nov 12 at 22:49


















up vote
11
down vote













Move the GFCI



GFCIs have sensitive electronic components, as you found out the hard way. A regular outlet does not. If you can move the GFCI protection to an indoor location and then replace this with a regular receptacle, that would solve the problem permanently while still protecting against ground faults. Two options:




  • Earlier in the chain. If there are other receptacles as part of this circuit before this outlet (e.g., possibly the bathroom that is on the same circuit), replace one of those with a GFCI receptacle. Just make sure that you use line vs. load correctly so that this receptacle is protected (on load screws).


  • At the breaker. If you have sufficient space in your panel, replace the regular breaker with a GFCI breaker. That will protect the entire circuit.



As already noted, you should have an in-use cover on any outside outlet. This will help prevent nuisance trips due to moisture, though it is not a 100% cure-all and therefore moving the GFCI inside makes sense in any case.



Based on additional comments: It appears that the bathroom receptacle already has GFCI. If that is the case then (a) no need for a GFCI breaker and (b) need to check whether the outdoor receptacle (and any others in the circuit) is pigtailed to share the line connection or is actually using load. If the outdoor receptacle connects via load then it is already protected. Open up the bathroom receptacle box. If there are wires on both line and load, then wire up an ordinary receptacle in the outdoor location. Make sure it works. Then press the TEST button in the bathroom.



If the outdoor receptacle responds to the bathroom TEST button (i.e., when TEST is pressed, both bathroom & outdoor have no power, when RESET is pressed both bathroom & outdoor have power again) then you do not need a GFCI on the outdoor receptacle because it is already protected in the bathroom. Only one is needed but keep in mind that it protects "outward" - i.e., if the sequence is breaker->bathroom->outdoor then a GFCI breaker or a bathroom GFCI will protect bathroom and outdoor, but a GFCI outdoor will NOT protect the bathroom (though as we've discussed, you shouldn't put the GFCI outdoors anyway).






share|improve this answer



















  • 2




    Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
    – Ed Beal
    Nov 12 at 17:29






  • 3




    The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
    – Harper
    Nov 12 at 18:24










  • @manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
    – almarshall
    Nov 12 at 20:32






  • 1




    An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
    – manassehkatz
    Nov 12 at 20:48






  • 1




    You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
    – Ed Beal
    Nov 13 at 14:14


















up vote
2
down vote













Exploding and burning equipment is not normal at all. Except for cases you are pyrotechnist and it burned/exploded intentionally.



There is no shame to admit limited knowledge about electricity and call an electrician to fix the issue. To be honest, this is the only sane way to go, unless you know what you are doing and why you are doing it bloody well. Shame is when one does not admit lacking knowledge and sets own house on fire accidentaly.



Any receptacle, connection and device shall be tested for a proper IP code to its use. Indoor receptacles are sufficient with code IP30 (protection against tools with diameter greater than 2.5 mm and no protection against water), for outdoor receptacles look for code IP65, IP68 for being sure. Materials are usualy not the concern here - the interior shall be dust-free and dry and the parts are well insulated when dry and clean (IP00).



Your receptacle was IP30 at most - no dust protection and no water protection. What happened to you was crossing the circuits within your receptacle by rainwater mixed with dust. This is conductive enough to shortcircuit anything behind the receptacle while resistant enough to heat significantly.



As other sugested, move the GFCI circuit indoors and use common receptacle outdors. The whole receptacle setup - box, receptacle and wiring - shall be code IP65 and more. If you move the GFCI only your breakers will be down quite often. The only improvement will be not burning the GFCI to ashes.






share|improve this answer























  • This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
    – Ed Beal
    Nov 13 at 14:18






  • 2




    In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
    – blockcipher
    Nov 13 at 18:17










  • @blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
    – Ed Beal
    Nov 13 at 18:35










  • I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
    – blockcipher
    Nov 15 at 12:24











Your Answer








StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});

function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});


}
});






almarshall is a new contributor. Be nice, and check out our Code of Conduct.










 

draft saved


draft discarded


















StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150437%2fis-it-normal-for-gfci-receptacles-to-explode-and-burn%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown

























3 Answers
3






active

oldest

votes








3 Answers
3






active

oldest

votes









active

oldest

votes






active

oldest

votes








up vote
21
down vote













This happens all the time if an exterior GFCI is not weather-resistant. I've never had a weather resistant GFCI go up in smoke.



Yes, they can be in a metal box, but they still should be marked WR (weather resistant) - this means the electronics inside are coated to reduce the chances of moisture causing exactly what happened with your GFCI.



If it had shorted to the box, the metal screw would have arced and tripped the breaker. If it had shorted on the load side, it would have tripped the GFCI. But, in this case, enough moisture got in and the electronics shorted and let the magic smoke out.



Last item on the list is that it should have an in-use cover or an extra duty cover, that allows a cord to be plugged in with the cover protecting from rain.



In this case, replace your GFCI with a WR rated GFCI and add an in-use cover to greatly reduce the chance of this happening again. In some jurisdictions the local ordinances require the outlet itself to be GFCI so it can be reset (not running cords inside because of tripping the GFCI in wet grass with an electric mower is the "why" the inspector told me).






share|improve this answer



















  • 2




    This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
    – Eric Lippert
    Nov 12 at 17:27










  • Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
    – almarshall
    Nov 12 at 20:26










  • Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
    – Perkins
    Nov 12 at 22:26










  • @almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
    – Crowley
    Nov 12 at 22:39










  • As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
    – Ed Beal
    Nov 12 at 22:49















up vote
21
down vote













This happens all the time if an exterior GFCI is not weather-resistant. I've never had a weather resistant GFCI go up in smoke.



Yes, they can be in a metal box, but they still should be marked WR (weather resistant) - this means the electronics inside are coated to reduce the chances of moisture causing exactly what happened with your GFCI.



If it had shorted to the box, the metal screw would have arced and tripped the breaker. If it had shorted on the load side, it would have tripped the GFCI. But, in this case, enough moisture got in and the electronics shorted and let the magic smoke out.



Last item on the list is that it should have an in-use cover or an extra duty cover, that allows a cord to be plugged in with the cover protecting from rain.



In this case, replace your GFCI with a WR rated GFCI and add an in-use cover to greatly reduce the chance of this happening again. In some jurisdictions the local ordinances require the outlet itself to be GFCI so it can be reset (not running cords inside because of tripping the GFCI in wet grass with an electric mower is the "why" the inspector told me).






share|improve this answer



















  • 2




    This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
    – Eric Lippert
    Nov 12 at 17:27










  • Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
    – almarshall
    Nov 12 at 20:26










  • Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
    – Perkins
    Nov 12 at 22:26










  • @almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
    – Crowley
    Nov 12 at 22:39










  • As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
    – Ed Beal
    Nov 12 at 22:49













up vote
21
down vote










up vote
21
down vote









This happens all the time if an exterior GFCI is not weather-resistant. I've never had a weather resistant GFCI go up in smoke.



Yes, they can be in a metal box, but they still should be marked WR (weather resistant) - this means the electronics inside are coated to reduce the chances of moisture causing exactly what happened with your GFCI.



If it had shorted to the box, the metal screw would have arced and tripped the breaker. If it had shorted on the load side, it would have tripped the GFCI. But, in this case, enough moisture got in and the electronics shorted and let the magic smoke out.



Last item on the list is that it should have an in-use cover or an extra duty cover, that allows a cord to be plugged in with the cover protecting from rain.



In this case, replace your GFCI with a WR rated GFCI and add an in-use cover to greatly reduce the chance of this happening again. In some jurisdictions the local ordinances require the outlet itself to be GFCI so it can be reset (not running cords inside because of tripping the GFCI in wet grass with an electric mower is the "why" the inspector told me).






share|improve this answer














This happens all the time if an exterior GFCI is not weather-resistant. I've never had a weather resistant GFCI go up in smoke.



Yes, they can be in a metal box, but they still should be marked WR (weather resistant) - this means the electronics inside are coated to reduce the chances of moisture causing exactly what happened with your GFCI.



If it had shorted to the box, the metal screw would have arced and tripped the breaker. If it had shorted on the load side, it would have tripped the GFCI. But, in this case, enough moisture got in and the electronics shorted and let the magic smoke out.



Last item on the list is that it should have an in-use cover or an extra duty cover, that allows a cord to be plugged in with the cover protecting from rain.



In this case, replace your GFCI with a WR rated GFCI and add an in-use cover to greatly reduce the chance of this happening again. In some jurisdictions the local ordinances require the outlet itself to be GFCI so it can be reset (not running cords inside because of tripping the GFCI in wet grass with an electric mower is the "why" the inspector told me).







share|improve this answer














share|improve this answer



share|improve this answer








edited Nov 13 at 17:13









Daniel Griscom

4,47662236




4,47662236










answered Nov 12 at 14:54









Ed Beal

28.1k11841




28.1k11841








  • 2




    This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
    – Eric Lippert
    Nov 12 at 17:27










  • Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
    – almarshall
    Nov 12 at 20:26










  • Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
    – Perkins
    Nov 12 at 22:26










  • @almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
    – Crowley
    Nov 12 at 22:39










  • As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
    – Ed Beal
    Nov 12 at 22:49














  • 2




    This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
    – Eric Lippert
    Nov 12 at 17:27










  • Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
    – almarshall
    Nov 12 at 20:26










  • Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
    – Perkins
    Nov 12 at 22:26










  • @almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
    – Crowley
    Nov 12 at 22:39










  • As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
    – Ed Beal
    Nov 12 at 22:49








2




2




This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
– Eric Lippert
Nov 12 at 17:27




This exact same situation happened to me with a weather-rated box. As is often the case with catastrophic failures of safety systems, multiple things had to go wrong at once. In my case, the box was properly sealed from the outside but where the wires entered the box from inside the wall was not sealed; the GFCI was near a hose, and the hose fitting had a slow leak inside the wall that dripped onto a wire, that led to the GFCI, and got it wet without ever causing a ground fault. Had I not smelled the burning plastic and immediately turned off the power, bad things could have happened.
– Eric Lippert
Nov 12 at 17:27












Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
– almarshall
Nov 12 at 20:26




Thank you for the advice, do I have any concern of damage to the wires outside of the box? I am comfortable replacing an outlet (using the appropriate rated outlet and in-use cover) but I was concerned that the heat might have cause some damage to the wire further in the wall.
– almarshall
Nov 12 at 20:26












Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
– Perkins
Nov 12 at 22:26




Note that most GFCI outlets can be installed to protect additional "downstream" outlets. On my house the GFCI are all indoors, but then wired to protect the outdoor ones. This is occasionally inconvenient as I don't always remember which ones protect what, but the expensive outlets are safe from water and people driving away without unplugging their block heater.
– Perkins
Nov 12 at 22:26












@almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
– Crowley
Nov 12 at 22:39




@almarshall The wires should be rated with safety margin - you'd rather see a faulty device on fire than a wires in your wall. Only the terminals were at risk and the spread of the damage is limitted by heat conductivity of the wire and ambient temperature.
– Crowley
Nov 12 at 22:39












As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
– Ed Beal
Nov 12 at 22:49




As far as wire damage it would not extend outside the clamps. I would check the insulation at the clamps in the back of the box if it is good there and to the ends of the wires put in a new WR GFCI and in-use cover and power it up.
– Ed Beal
Nov 12 at 22:49












up vote
11
down vote













Move the GFCI



GFCIs have sensitive electronic components, as you found out the hard way. A regular outlet does not. If you can move the GFCI protection to an indoor location and then replace this with a regular receptacle, that would solve the problem permanently while still protecting against ground faults. Two options:




  • Earlier in the chain. If there are other receptacles as part of this circuit before this outlet (e.g., possibly the bathroom that is on the same circuit), replace one of those with a GFCI receptacle. Just make sure that you use line vs. load correctly so that this receptacle is protected (on load screws).


  • At the breaker. If you have sufficient space in your panel, replace the regular breaker with a GFCI breaker. That will protect the entire circuit.



As already noted, you should have an in-use cover on any outside outlet. This will help prevent nuisance trips due to moisture, though it is not a 100% cure-all and therefore moving the GFCI inside makes sense in any case.



Based on additional comments: It appears that the bathroom receptacle already has GFCI. If that is the case then (a) no need for a GFCI breaker and (b) need to check whether the outdoor receptacle (and any others in the circuit) is pigtailed to share the line connection or is actually using load. If the outdoor receptacle connects via load then it is already protected. Open up the bathroom receptacle box. If there are wires on both line and load, then wire up an ordinary receptacle in the outdoor location. Make sure it works. Then press the TEST button in the bathroom.



If the outdoor receptacle responds to the bathroom TEST button (i.e., when TEST is pressed, both bathroom & outdoor have no power, when RESET is pressed both bathroom & outdoor have power again) then you do not need a GFCI on the outdoor receptacle because it is already protected in the bathroom. Only one is needed but keep in mind that it protects "outward" - i.e., if the sequence is breaker->bathroom->outdoor then a GFCI breaker or a bathroom GFCI will protect bathroom and outdoor, but a GFCI outdoor will NOT protect the bathroom (though as we've discussed, you shouldn't put the GFCI outdoors anyway).






share|improve this answer



















  • 2




    Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
    – Ed Beal
    Nov 12 at 17:29






  • 3




    The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
    – Harper
    Nov 12 at 18:24










  • @manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
    – almarshall
    Nov 12 at 20:32






  • 1




    An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
    – manassehkatz
    Nov 12 at 20:48






  • 1




    You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
    – Ed Beal
    Nov 13 at 14:14















up vote
11
down vote













Move the GFCI



GFCIs have sensitive electronic components, as you found out the hard way. A regular outlet does not. If you can move the GFCI protection to an indoor location and then replace this with a regular receptacle, that would solve the problem permanently while still protecting against ground faults. Two options:




  • Earlier in the chain. If there are other receptacles as part of this circuit before this outlet (e.g., possibly the bathroom that is on the same circuit), replace one of those with a GFCI receptacle. Just make sure that you use line vs. load correctly so that this receptacle is protected (on load screws).


  • At the breaker. If you have sufficient space in your panel, replace the regular breaker with a GFCI breaker. That will protect the entire circuit.



As already noted, you should have an in-use cover on any outside outlet. This will help prevent nuisance trips due to moisture, though it is not a 100% cure-all and therefore moving the GFCI inside makes sense in any case.



Based on additional comments: It appears that the bathroom receptacle already has GFCI. If that is the case then (a) no need for a GFCI breaker and (b) need to check whether the outdoor receptacle (and any others in the circuit) is pigtailed to share the line connection or is actually using load. If the outdoor receptacle connects via load then it is already protected. Open up the bathroom receptacle box. If there are wires on both line and load, then wire up an ordinary receptacle in the outdoor location. Make sure it works. Then press the TEST button in the bathroom.



If the outdoor receptacle responds to the bathroom TEST button (i.e., when TEST is pressed, both bathroom & outdoor have no power, when RESET is pressed both bathroom & outdoor have power again) then you do not need a GFCI on the outdoor receptacle because it is already protected in the bathroom. Only one is needed but keep in mind that it protects "outward" - i.e., if the sequence is breaker->bathroom->outdoor then a GFCI breaker or a bathroom GFCI will protect bathroom and outdoor, but a GFCI outdoor will NOT protect the bathroom (though as we've discussed, you shouldn't put the GFCI outdoors anyway).






share|improve this answer



















  • 2




    Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
    – Ed Beal
    Nov 12 at 17:29






  • 3




    The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
    – Harper
    Nov 12 at 18:24










  • @manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
    – almarshall
    Nov 12 at 20:32






  • 1




    An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
    – manassehkatz
    Nov 12 at 20:48






  • 1




    You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
    – Ed Beal
    Nov 13 at 14:14













up vote
11
down vote










up vote
11
down vote









Move the GFCI



GFCIs have sensitive electronic components, as you found out the hard way. A regular outlet does not. If you can move the GFCI protection to an indoor location and then replace this with a regular receptacle, that would solve the problem permanently while still protecting against ground faults. Two options:




  • Earlier in the chain. If there are other receptacles as part of this circuit before this outlet (e.g., possibly the bathroom that is on the same circuit), replace one of those with a GFCI receptacle. Just make sure that you use line vs. load correctly so that this receptacle is protected (on load screws).


  • At the breaker. If you have sufficient space in your panel, replace the regular breaker with a GFCI breaker. That will protect the entire circuit.



As already noted, you should have an in-use cover on any outside outlet. This will help prevent nuisance trips due to moisture, though it is not a 100% cure-all and therefore moving the GFCI inside makes sense in any case.



Based on additional comments: It appears that the bathroom receptacle already has GFCI. If that is the case then (a) no need for a GFCI breaker and (b) need to check whether the outdoor receptacle (and any others in the circuit) is pigtailed to share the line connection or is actually using load. If the outdoor receptacle connects via load then it is already protected. Open up the bathroom receptacle box. If there are wires on both line and load, then wire up an ordinary receptacle in the outdoor location. Make sure it works. Then press the TEST button in the bathroom.



If the outdoor receptacle responds to the bathroom TEST button (i.e., when TEST is pressed, both bathroom & outdoor have no power, when RESET is pressed both bathroom & outdoor have power again) then you do not need a GFCI on the outdoor receptacle because it is already protected in the bathroom. Only one is needed but keep in mind that it protects "outward" - i.e., if the sequence is breaker->bathroom->outdoor then a GFCI breaker or a bathroom GFCI will protect bathroom and outdoor, but a GFCI outdoor will NOT protect the bathroom (though as we've discussed, you shouldn't put the GFCI outdoors anyway).






share|improve this answer














Move the GFCI



GFCIs have sensitive electronic components, as you found out the hard way. A regular outlet does not. If you can move the GFCI protection to an indoor location and then replace this with a regular receptacle, that would solve the problem permanently while still protecting against ground faults. Two options:




  • Earlier in the chain. If there are other receptacles as part of this circuit before this outlet (e.g., possibly the bathroom that is on the same circuit), replace one of those with a GFCI receptacle. Just make sure that you use line vs. load correctly so that this receptacle is protected (on load screws).


  • At the breaker. If you have sufficient space in your panel, replace the regular breaker with a GFCI breaker. That will protect the entire circuit.



As already noted, you should have an in-use cover on any outside outlet. This will help prevent nuisance trips due to moisture, though it is not a 100% cure-all and therefore moving the GFCI inside makes sense in any case.



Based on additional comments: It appears that the bathroom receptacle already has GFCI. If that is the case then (a) no need for a GFCI breaker and (b) need to check whether the outdoor receptacle (and any others in the circuit) is pigtailed to share the line connection or is actually using load. If the outdoor receptacle connects via load then it is already protected. Open up the bathroom receptacle box. If there are wires on both line and load, then wire up an ordinary receptacle in the outdoor location. Make sure it works. Then press the TEST button in the bathroom.



If the outdoor receptacle responds to the bathroom TEST button (i.e., when TEST is pressed, both bathroom & outdoor have no power, when RESET is pressed both bathroom & outdoor have power again) then you do not need a GFCI on the outdoor receptacle because it is already protected in the bathroom. Only one is needed but keep in mind that it protects "outward" - i.e., if the sequence is breaker->bathroom->outdoor then a GFCI breaker or a bathroom GFCI will protect bathroom and outdoor, but a GFCI outdoor will NOT protect the bathroom (though as we've discussed, you shouldn't put the GFCI outdoors anyway).







share|improve this answer














share|improve this answer



share|improve this answer








edited Nov 12 at 21:45

























answered Nov 12 at 15:15









manassehkatz

4,636624




4,636624








  • 2




    Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
    – Ed Beal
    Nov 12 at 17:29






  • 3




    The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
    – Harper
    Nov 12 at 18:24










  • @manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
    – almarshall
    Nov 12 at 20:32






  • 1




    An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
    – manassehkatz
    Nov 12 at 20:48






  • 1




    You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
    – Ed Beal
    Nov 13 at 14:14














  • 2




    Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
    – Ed Beal
    Nov 12 at 17:29






  • 3




    The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
    – Harper
    Nov 12 at 18:24










  • @manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
    – almarshall
    Nov 12 at 20:32






  • 1




    An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
    – manassehkatz
    Nov 12 at 20:48






  • 1




    You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
    – Ed Beal
    Nov 13 at 14:14








2




2




Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
– Ed Beal
Nov 12 at 17:29




Add an in-use cover and this would be a better answer because moisture getting into an exterior outlet can trip the remote mounted GFCI.
– Ed Beal
Nov 12 at 17:29




3




3




The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
– Harper
Nov 12 at 18:24




The in-use cover is required by Code (even though they don't work) and having the indoor GFCI trip is a vastly better outcome than OP.
– Harper
Nov 12 at 18:24












@manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
– almarshall
Nov 12 at 20:32




@manassehkatz If I am replacing the breaker is it worth getting a dual function AFCI/GFCI or is the GFCI generally considered suffcient?
– almarshall
Nov 12 at 20:32




1




1




An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
– manassehkatz
Nov 12 at 20:48




An AFCI protects against different types of problems than GFCI. Is it probably a good idea, yes. But the key issue with both an outdoor outlet and a bathroom outlet is to protect against ground faults, which is what GFCI does. AFCI protects primarily against wiring faults, which can happen anywhere - more of a fire prevention issue than a life safety (electrical shock) issue.
– manassehkatz
Nov 12 at 20:48




1




1




You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
– Ed Beal
Nov 13 at 14:14




You might find AFCI functionality to be problematic hair dryers and electric hand tools used outside can cause AFCI's to trip because they think the brushes in the motor are wiring failures. They have gotten better but I would use a GFCI only until they get the bugs out.
– Ed Beal
Nov 13 at 14:14










up vote
2
down vote













Exploding and burning equipment is not normal at all. Except for cases you are pyrotechnist and it burned/exploded intentionally.



There is no shame to admit limited knowledge about electricity and call an electrician to fix the issue. To be honest, this is the only sane way to go, unless you know what you are doing and why you are doing it bloody well. Shame is when one does not admit lacking knowledge and sets own house on fire accidentaly.



Any receptacle, connection and device shall be tested for a proper IP code to its use. Indoor receptacles are sufficient with code IP30 (protection against tools with diameter greater than 2.5 mm and no protection against water), for outdoor receptacles look for code IP65, IP68 for being sure. Materials are usualy not the concern here - the interior shall be dust-free and dry and the parts are well insulated when dry and clean (IP00).



Your receptacle was IP30 at most - no dust protection and no water protection. What happened to you was crossing the circuits within your receptacle by rainwater mixed with dust. This is conductive enough to shortcircuit anything behind the receptacle while resistant enough to heat significantly.



As other sugested, move the GFCI circuit indoors and use common receptacle outdors. The whole receptacle setup - box, receptacle and wiring - shall be code IP65 and more. If you move the GFCI only your breakers will be down quite often. The only improvement will be not burning the GFCI to ashes.






share|improve this answer























  • This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
    – Ed Beal
    Nov 13 at 14:18






  • 2




    In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
    – blockcipher
    Nov 13 at 18:17










  • @blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
    – Ed Beal
    Nov 13 at 18:35










  • I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
    – blockcipher
    Nov 15 at 12:24















up vote
2
down vote













Exploding and burning equipment is not normal at all. Except for cases you are pyrotechnist and it burned/exploded intentionally.



There is no shame to admit limited knowledge about electricity and call an electrician to fix the issue. To be honest, this is the only sane way to go, unless you know what you are doing and why you are doing it bloody well. Shame is when one does not admit lacking knowledge and sets own house on fire accidentaly.



Any receptacle, connection and device shall be tested for a proper IP code to its use. Indoor receptacles are sufficient with code IP30 (protection against tools with diameter greater than 2.5 mm and no protection against water), for outdoor receptacles look for code IP65, IP68 for being sure. Materials are usualy not the concern here - the interior shall be dust-free and dry and the parts are well insulated when dry and clean (IP00).



Your receptacle was IP30 at most - no dust protection and no water protection. What happened to you was crossing the circuits within your receptacle by rainwater mixed with dust. This is conductive enough to shortcircuit anything behind the receptacle while resistant enough to heat significantly.



As other sugested, move the GFCI circuit indoors and use common receptacle outdors. The whole receptacle setup - box, receptacle and wiring - shall be code IP65 and more. If you move the GFCI only your breakers will be down quite often. The only improvement will be not burning the GFCI to ashes.






share|improve this answer























  • This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
    – Ed Beal
    Nov 13 at 14:18






  • 2




    In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
    – blockcipher
    Nov 13 at 18:17










  • @blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
    – Ed Beal
    Nov 13 at 18:35










  • I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
    – blockcipher
    Nov 15 at 12:24













up vote
2
down vote










up vote
2
down vote









Exploding and burning equipment is not normal at all. Except for cases you are pyrotechnist and it burned/exploded intentionally.



There is no shame to admit limited knowledge about electricity and call an electrician to fix the issue. To be honest, this is the only sane way to go, unless you know what you are doing and why you are doing it bloody well. Shame is when one does not admit lacking knowledge and sets own house on fire accidentaly.



Any receptacle, connection and device shall be tested for a proper IP code to its use. Indoor receptacles are sufficient with code IP30 (protection against tools with diameter greater than 2.5 mm and no protection against water), for outdoor receptacles look for code IP65, IP68 for being sure. Materials are usualy not the concern here - the interior shall be dust-free and dry and the parts are well insulated when dry and clean (IP00).



Your receptacle was IP30 at most - no dust protection and no water protection. What happened to you was crossing the circuits within your receptacle by rainwater mixed with dust. This is conductive enough to shortcircuit anything behind the receptacle while resistant enough to heat significantly.



As other sugested, move the GFCI circuit indoors and use common receptacle outdors. The whole receptacle setup - box, receptacle and wiring - shall be code IP65 and more. If you move the GFCI only your breakers will be down quite often. The only improvement will be not burning the GFCI to ashes.






share|improve this answer














Exploding and burning equipment is not normal at all. Except for cases you are pyrotechnist and it burned/exploded intentionally.



There is no shame to admit limited knowledge about electricity and call an electrician to fix the issue. To be honest, this is the only sane way to go, unless you know what you are doing and why you are doing it bloody well. Shame is when one does not admit lacking knowledge and sets own house on fire accidentaly.



Any receptacle, connection and device shall be tested for a proper IP code to its use. Indoor receptacles are sufficient with code IP30 (protection against tools with diameter greater than 2.5 mm and no protection against water), for outdoor receptacles look for code IP65, IP68 for being sure. Materials are usualy not the concern here - the interior shall be dust-free and dry and the parts are well insulated when dry and clean (IP00).



Your receptacle was IP30 at most - no dust protection and no water protection. What happened to you was crossing the circuits within your receptacle by rainwater mixed with dust. This is conductive enough to shortcircuit anything behind the receptacle while resistant enough to heat significantly.



As other sugested, move the GFCI circuit indoors and use common receptacle outdors. The whole receptacle setup - box, receptacle and wiring - shall be code IP65 and more. If you move the GFCI only your breakers will be down quite often. The only improvement will be not burning the GFCI to ashes.







share|improve this answer














share|improve this answer



share|improve this answer








edited Nov 15 at 13:53

























answered Nov 12 at 22:34









Crowley

64527




64527












  • This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
    – Ed Beal
    Nov 13 at 14:18






  • 2




    In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
    – blockcipher
    Nov 13 at 18:17










  • @blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
    – Ed Beal
    Nov 13 at 18:35










  • I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
    – blockcipher
    Nov 15 at 12:24


















  • This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
    – Ed Beal
    Nov 13 at 14:18






  • 2




    In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
    – blockcipher
    Nov 13 at 18:17










  • @blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
    – Ed Beal
    Nov 13 at 18:35










  • I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
    – blockcipher
    Nov 15 at 12:24
















This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
– Ed Beal
Nov 13 at 14:18




This is a DIY site telling everyone to have it done professionally is not what we are about. As several answers specify in-use covers or extra duty these covers are considered water proof by code.
– Ed Beal
Nov 13 at 14:18




2




2




In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
– blockcipher
Nov 13 at 18:17




In this case, as someone who used to work as an electrician, I think this should be looked at by a professional. I can't tell from the pictures exactly how bad the damage is, but if I had to guess, the wires inside the box are probably damaged and may need to be replaced. An expert will know better than most people on this site. If I was confident it was just the outlet, then yes, replace the GFCI and the cover. However, I see a melted wire nut in the last picture, which concerns me greatly. Seeing that makes me thing the wires are damaged as well.
– blockcipher
Nov 13 at 18:17












@blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
– Ed Beal
Nov 13 at 18:35




@blockcipher the OP stated he was comfortable doing the repair and asked the right questions about the insulation so I believe he is competent to do the repair, this is what this site is all about no electrician is really needed on site to verify the repair and there are at least 2 responding to this that regularly assist home owners in doing there own repairs.
– Ed Beal
Nov 13 at 18:35












I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
– blockcipher
Nov 15 at 12:24




I understand what you're saying and under many other circumstances, I'd be on board with the homeowner doing it themselves, however, in this case I'm highly recommending on the side of caution since I cannot assess the condition of the wires themselves. I do see the other comments related to this and I do agree you have to examine the wires in the connector to assess the damage. I just think that someone with experience would do a better job of assessing the damage to prevent future problems. Ultimately, it is up to the homeowner if they wish to attempt it themselves.
– blockcipher
Nov 15 at 12:24










almarshall is a new contributor. Be nice, and check out our Code of Conduct.










 

draft saved


draft discarded


















almarshall is a new contributor. Be nice, and check out our Code of Conduct.













almarshall is a new contributor. Be nice, and check out our Code of Conduct.












almarshall is a new contributor. Be nice, and check out our Code of Conduct.















 


draft saved


draft discarded














StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150437%2fis-it-normal-for-gfci-receptacles-to-explode-and-burn%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







Popular posts from this blog

How to change which sound is reproduced for terminal bell?

Can I use Tabulator js library in my java Spring + Thymeleaf project?

Title Spacing in Bjornstrup Chapter, Removing Chapter Number From Contents