Is corrosion inhibitor paste conductive?
I bought some Alumiconn terminals to connect 3 copper AWG 10 wires (more secure than wire nuts):
There is corrosion inhibitor paste inside each hole. Amazon product description described it thus: "Ports of connectors contain a layer of corrosion inhibitor that provides resistance from oxidation."
Can these be detrimental to the conduction of the copper (maybe forming insulator layers)?
Also these can be used in all pure copper wires (all of the 3 wires) right?
electrical
add a comment |
I bought some Alumiconn terminals to connect 3 copper AWG 10 wires (more secure than wire nuts):
There is corrosion inhibitor paste inside each hole. Amazon product description described it thus: "Ports of connectors contain a layer of corrosion inhibitor that provides resistance from oxidation."
Can these be detrimental to the conduction of the copper (maybe forming insulator layers)?
Also these can be used in all pure copper wires (all of the 3 wires) right?
electrical
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
1
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29
add a comment |
I bought some Alumiconn terminals to connect 3 copper AWG 10 wires (more secure than wire nuts):
There is corrosion inhibitor paste inside each hole. Amazon product description described it thus: "Ports of connectors contain a layer of corrosion inhibitor that provides resistance from oxidation."
Can these be detrimental to the conduction of the copper (maybe forming insulator layers)?
Also these can be used in all pure copper wires (all of the 3 wires) right?
electrical
I bought some Alumiconn terminals to connect 3 copper AWG 10 wires (more secure than wire nuts):
There is corrosion inhibitor paste inside each hole. Amazon product description described it thus: "Ports of connectors contain a layer of corrosion inhibitor that provides resistance from oxidation."
Can these be detrimental to the conduction of the copper (maybe forming insulator layers)?
Also these can be used in all pure copper wires (all of the 3 wires) right?
electrical
electrical
edited Feb 21 at 13:55
isherwood
48.8k456124
48.8k456124
asked Feb 21 at 12:20
JtlJtl
1198
1198
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
1
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29
add a comment |
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
1
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
1
1
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29
add a comment |
2 Answers
2
active
oldest
votes
The paste inside the AlumiConn does not negatively affect the electrical connection. When the screw is tightened the paste between wire and the metal screw and the metal body of the AlumiConn is squeezed out.
You can use these for copper wires, but it is really unnecessary. In the upper picture the end of the wire is stripped too long. The insulation on the wire is supposed to be inside the skirt of the insulation on the AlumiConn. I think there is a strip gauge on back of the Alumiconn.
EDIT Memory failure! Just looked at my stash of AlumiConns and there's no strip gauge on the insulation.
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
add a comment |
It depends on the type of anti oxide compound used, 2 of the 3 types I use are conductive 1 is not. Some folks say it is not needed but most lugs today are aluminum and a little deox on the wires will improve the long life especially if in a coastal region. I recently had to rebuild a panel that had all copper wire with aluminum lugs the lugs showed hot with thermal imaging camera. I removed the conductors and found a large amount of oxide on the lug to wire connection area, cleaned everything up and coated with deox. Let the system run for a day and rechecked it is now running 30°F (17°C) cooler.
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
add a comment |
Your Answer
StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});
function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});
}
});
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f158200%2fis-corrosion-inhibitor-paste-conductive%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
2 Answers
2
active
oldest
votes
2 Answers
2
active
oldest
votes
active
oldest
votes
active
oldest
votes
The paste inside the AlumiConn does not negatively affect the electrical connection. When the screw is tightened the paste between wire and the metal screw and the metal body of the AlumiConn is squeezed out.
You can use these for copper wires, but it is really unnecessary. In the upper picture the end of the wire is stripped too long. The insulation on the wire is supposed to be inside the skirt of the insulation on the AlumiConn. I think there is a strip gauge on back of the Alumiconn.
EDIT Memory failure! Just looked at my stash of AlumiConns and there's no strip gauge on the insulation.
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
add a comment |
The paste inside the AlumiConn does not negatively affect the electrical connection. When the screw is tightened the paste between wire and the metal screw and the metal body of the AlumiConn is squeezed out.
You can use these for copper wires, but it is really unnecessary. In the upper picture the end of the wire is stripped too long. The insulation on the wire is supposed to be inside the skirt of the insulation on the AlumiConn. I think there is a strip gauge on back of the Alumiconn.
EDIT Memory failure! Just looked at my stash of AlumiConns and there's no strip gauge on the insulation.
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
add a comment |
The paste inside the AlumiConn does not negatively affect the electrical connection. When the screw is tightened the paste between wire and the metal screw and the metal body of the AlumiConn is squeezed out.
You can use these for copper wires, but it is really unnecessary. In the upper picture the end of the wire is stripped too long. The insulation on the wire is supposed to be inside the skirt of the insulation on the AlumiConn. I think there is a strip gauge on back of the Alumiconn.
EDIT Memory failure! Just looked at my stash of AlumiConns and there's no strip gauge on the insulation.
The paste inside the AlumiConn does not negatively affect the electrical connection. When the screw is tightened the paste between wire and the metal screw and the metal body of the AlumiConn is squeezed out.
You can use these for copper wires, but it is really unnecessary. In the upper picture the end of the wire is stripped too long. The insulation on the wire is supposed to be inside the skirt of the insulation on the AlumiConn. I think there is a strip gauge on back of the Alumiconn.
EDIT Memory failure! Just looked at my stash of AlumiConns and there's no strip gauge on the insulation.
edited Feb 21 at 14:01
answered Feb 21 at 13:49
Jim StewartJim Stewart
11.6k11232
11.6k11232
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
add a comment |
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
I was just testing them and pulled it a bit when I tried to remove the third wire but didn't have the screwdriver. See imagizer.imageshack.com/img923/8660/ctWiTe.jpg also I just received the Torque screwdriver and the Alumiconn just today from amazon
– Jtl
Feb 21 at 14:02
8
8
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
Good answer, but I'd add safety note that if you are going to rely on it to be an insulator, assume it is conductive, and if you are going to rely on it being conductor, assume it's insulator. For example, tighten screws for good contact, do not assume paste would help, but also do not touch paste in the empty receptacle, assume it may be "hot".
– Mołot
Feb 21 at 15:06
1
1
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
I assume that none of the various anti-oxidant pastes are conducting. The reason I think so is that the base is a nonconducting silicone grease (earlier ones perhaps petroleum) and so if it were conducting the current would be carried by ions moving in the base oil. At the metallic interface there would be corrosion if there was a current being carried from the metal to the gel. The purpose of the paste is to prevent oxygen from the atmosphere from reaching the reactive surface of aluminum wire or an aluminum fitting.
– Jim Stewart
Feb 21 at 17:51
2
2
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
Jim, they may not show conductive with a low voltage ohm meter but checking with a merger some are the clear anti oxide paste I use on 34.5kv lines to my transformers requires non conductive paste , got tapped by An inspector on that one and had to clean the lugs and wires, I did not realize that some were conductive prior to that time .
– Ed Beal
Feb 21 at 19:22
1
1
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
I have no specific knowledge about whether these anti-oxidant greases are in fact non-conductive. I was just going on my (elementary) understanding of electro-chemistry. Clearly some greases used to mount devices to heat sinks are designed to conduct heat. I can't imagine any antioxidant joint compound being electrically conductive, but I have no professional expertise in this.
– Jim Stewart
Feb 21 at 21:09
add a comment |
It depends on the type of anti oxide compound used, 2 of the 3 types I use are conductive 1 is not. Some folks say it is not needed but most lugs today are aluminum and a little deox on the wires will improve the long life especially if in a coastal region. I recently had to rebuild a panel that had all copper wire with aluminum lugs the lugs showed hot with thermal imaging camera. I removed the conductors and found a large amount of oxide on the lug to wire connection area, cleaned everything up and coated with deox. Let the system run for a day and rechecked it is now running 30°F (17°C) cooler.
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
add a comment |
It depends on the type of anti oxide compound used, 2 of the 3 types I use are conductive 1 is not. Some folks say it is not needed but most lugs today are aluminum and a little deox on the wires will improve the long life especially if in a coastal region. I recently had to rebuild a panel that had all copper wire with aluminum lugs the lugs showed hot with thermal imaging camera. I removed the conductors and found a large amount of oxide on the lug to wire connection area, cleaned everything up and coated with deox. Let the system run for a day and rechecked it is now running 30°F (17°C) cooler.
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
add a comment |
It depends on the type of anti oxide compound used, 2 of the 3 types I use are conductive 1 is not. Some folks say it is not needed but most lugs today are aluminum and a little deox on the wires will improve the long life especially if in a coastal region. I recently had to rebuild a panel that had all copper wire with aluminum lugs the lugs showed hot with thermal imaging camera. I removed the conductors and found a large amount of oxide on the lug to wire connection area, cleaned everything up and coated with deox. Let the system run for a day and rechecked it is now running 30°F (17°C) cooler.
It depends on the type of anti oxide compound used, 2 of the 3 types I use are conductive 1 is not. Some folks say it is not needed but most lugs today are aluminum and a little deox on the wires will improve the long life especially if in a coastal region. I recently had to rebuild a panel that had all copper wire with aluminum lugs the lugs showed hot with thermal imaging camera. I removed the conductors and found a large amount of oxide on the lug to wire connection area, cleaned everything up and coated with deox. Let the system run for a day and rechecked it is now running 30°F (17°C) cooler.
edited Feb 21 at 19:59
mskfisher
1105
1105
answered Feb 21 at 14:22
Ed BealEd Beal
33.5k12147
33.5k12147
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
add a comment |
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Is the proper procedure for making the connection of the heavy stranded wire from the meter into the main lugs of the panel to separate the strands and put antioxidant grease between and around the outer strands, then abrade the lugs with the antioxidant grease, then twist or compress the strands together enough to fit the wire into the lugs. Then tighten the lugs hard? to a specific torque? My panel has no grease on this connection that i can see. Guess I need to buy or borrow an infrared imaging thermometer. What voltage should there be between lug and wire with a significant load?
– Jim Stewart
Feb 21 at 22:29
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
Just coating the wires with a thin coat will do but I usually also do the lugs also and the threads of the set screw, in damp or salt conditions the anti oxide paste keeps the threads in good shape, in my case saving multi port large lugs costing over a hundred $ each.
– Ed Beal
Feb 22 at 1:02
add a comment |
Thanks for contributing an answer to Home Improvement Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f158200%2fis-corrosion-inhibitor-paste-conductive%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Would they sell it if it screwed up the connection? Electrical parts are some of the most tested and regulated merchandise on the planet, just behind medical devices...
– dandavis
Feb 21 at 16:07
1
After having seen terminal blocks being made of (expletive deleted) pot metal, two wire three prong IEC leads, and other things... I would say that there is a big market in things that screw up connections.
– rackandboneman
Feb 21 at 17:29