Is that a center tap tranformer just labelled differently?
$begingroup$
my transformer has a secondary winding of 0 - 12v - 24v
Is it just labelled differently and is it really a center tap where 12v would be the center, 0 would be -12v and 24 would be 12v?
Thanks!
transformer identification
$endgroup$
|
show 1 more comment
$begingroup$
my transformer has a secondary winding of 0 - 12v - 24v
Is it just labelled differently and is it really a center tap where 12v would be the center, 0 would be -12v and 24 would be 12v?
Thanks!
transformer identification
$endgroup$
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
3
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
2
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06
|
show 1 more comment
$begingroup$
my transformer has a secondary winding of 0 - 12v - 24v
Is it just labelled differently and is it really a center tap where 12v would be the center, 0 would be -12v and 24 would be 12v?
Thanks!
transformer identification
$endgroup$
my transformer has a secondary winding of 0 - 12v - 24v
Is it just labelled differently and is it really a center tap where 12v would be the center, 0 would be -12v and 24 would be 12v?
Thanks!
transformer identification
transformer identification
asked Feb 28 at 21:32
Mike Gleason jr CouturierMike Gleason jr Couturier
34918
34918
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
3
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
2
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06
|
show 1 more comment
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
3
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
2
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
3
3
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
2
2
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06
|
show 1 more comment
3 Answers
3
active
oldest
votes
$begingroup$
Not necessarily. If the transformer is rated to produce full output from either the 12V tap or the 24V tap, it could be that the winding from the 12 to 24V terminals is of a finer gage, since the current that could be drawn from the 24V tap would be half that you could draw at 12V. This you can determine by comparing the resistance of the 0-12 and 12-24 windings.
Would that matter for using it as a center-tapped +/- 12V transformer? Not much, the terminal voltage at the high side would be fractionally lower under load, but the overall heating compared to drawing the full power at a single tap would actually be less.
$endgroup$
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
add a comment |
$begingroup$
I would guess that yes, it is just a regular center tap transformer. Assuming that's the case:
The outputs will be AC, so -12V doesn't really have any meaning. The 12V here will be 12V AC, and the 24 will be 24V AC.
If you make the center tap 0, then "LABEL 0" will be 12V, and "LABEL 24" will also be 12V (but they will be out of phase with each other).
Based on the labeling, I think it's fairly certain that this is a regular transformer, but I would do some continuity tests just to make sure.
$endgroup$
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
add a comment |
$begingroup$
0V is arbitrary as it is floating secondary centre-tapped coil.
so you can relabel with 3 choices;
0 : 12Vac : 24Vac
12Vac : 0V : 12Vac +180 deg
24Vac : 12Vac : 0V
$endgroup$
add a comment |
Your Answer
StackExchange.ifUsing("editor", function () {
return StackExchange.using("mathjaxEditing", function () {
StackExchange.MarkdownEditor.creationCallbacks.add(function (editor, postfix) {
StackExchange.mathjaxEditing.prepareWmdForMathJax(editor, postfix, [["\$", "\$"]]);
});
});
}, "mathjax-editing");
StackExchange.ifUsing("editor", function () {
return StackExchange.using("schematics", function () {
StackExchange.schematics.init();
});
}, "cicuitlab");
StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "135"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});
function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});
}
});
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f424940%2fis-that-a-center-tap-tranformer-just-labelled-differently%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
3 Answers
3
active
oldest
votes
3 Answers
3
active
oldest
votes
active
oldest
votes
active
oldest
votes
$begingroup$
Not necessarily. If the transformer is rated to produce full output from either the 12V tap or the 24V tap, it could be that the winding from the 12 to 24V terminals is of a finer gage, since the current that could be drawn from the 24V tap would be half that you could draw at 12V. This you can determine by comparing the resistance of the 0-12 and 12-24 windings.
Would that matter for using it as a center-tapped +/- 12V transformer? Not much, the terminal voltage at the high side would be fractionally lower under load, but the overall heating compared to drawing the full power at a single tap would actually be less.
$endgroup$
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
add a comment |
$begingroup$
Not necessarily. If the transformer is rated to produce full output from either the 12V tap or the 24V tap, it could be that the winding from the 12 to 24V terminals is of a finer gage, since the current that could be drawn from the 24V tap would be half that you could draw at 12V. This you can determine by comparing the resistance of the 0-12 and 12-24 windings.
Would that matter for using it as a center-tapped +/- 12V transformer? Not much, the terminal voltage at the high side would be fractionally lower under load, but the overall heating compared to drawing the full power at a single tap would actually be less.
$endgroup$
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
add a comment |
$begingroup$
Not necessarily. If the transformer is rated to produce full output from either the 12V tap or the 24V tap, it could be that the winding from the 12 to 24V terminals is of a finer gage, since the current that could be drawn from the 24V tap would be half that you could draw at 12V. This you can determine by comparing the resistance of the 0-12 and 12-24 windings.
Would that matter for using it as a center-tapped +/- 12V transformer? Not much, the terminal voltage at the high side would be fractionally lower under load, but the overall heating compared to drawing the full power at a single tap would actually be less.
$endgroup$
Not necessarily. If the transformer is rated to produce full output from either the 12V tap or the 24V tap, it could be that the winding from the 12 to 24V terminals is of a finer gage, since the current that could be drawn from the 24V tap would be half that you could draw at 12V. This you can determine by comparing the resistance of the 0-12 and 12-24 windings.
Would that matter for using it as a center-tapped +/- 12V transformer? Not much, the terminal voltage at the high side would be fractionally lower under load, but the overall heating compared to drawing the full power at a single tap would actually be less.
answered Feb 28 at 21:49
Phil GPhil G
2,6921412
2,6921412
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
add a comment |
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
$begingroup$
I get 1 ohm resistence between 0 and 12, 1 ohm between 12 and 24 and 2 ohms between 0 and 24... So I guess this really is a center tap?
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:53
1
1
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
$begingroup$
I'd think so. While you can get more out of a given core (since you have to get all the windings through a fixed window size) by fine-tuning the wire sizes, there's the additional cost of winding different wire sizes, so keeping the windings the same is likely cheaper. More effective still for a 12V OR 24V secondary is to have two separate winding that can then be connected series or parallel to maximize winding utilization.
$endgroup$
– Phil G
Feb 28 at 22:19
add a comment |
$begingroup$
I would guess that yes, it is just a regular center tap transformer. Assuming that's the case:
The outputs will be AC, so -12V doesn't really have any meaning. The 12V here will be 12V AC, and the 24 will be 24V AC.
If you make the center tap 0, then "LABEL 0" will be 12V, and "LABEL 24" will also be 12V (but they will be out of phase with each other).
Based on the labeling, I think it's fairly certain that this is a regular transformer, but I would do some continuity tests just to make sure.
$endgroup$
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
add a comment |
$begingroup$
I would guess that yes, it is just a regular center tap transformer. Assuming that's the case:
The outputs will be AC, so -12V doesn't really have any meaning. The 12V here will be 12V AC, and the 24 will be 24V AC.
If you make the center tap 0, then "LABEL 0" will be 12V, and "LABEL 24" will also be 12V (but they will be out of phase with each other).
Based on the labeling, I think it's fairly certain that this is a regular transformer, but I would do some continuity tests just to make sure.
$endgroup$
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
add a comment |
$begingroup$
I would guess that yes, it is just a regular center tap transformer. Assuming that's the case:
The outputs will be AC, so -12V doesn't really have any meaning. The 12V here will be 12V AC, and the 24 will be 24V AC.
If you make the center tap 0, then "LABEL 0" will be 12V, and "LABEL 24" will also be 12V (but they will be out of phase with each other).
Based on the labeling, I think it's fairly certain that this is a regular transformer, but I would do some continuity tests just to make sure.
$endgroup$
I would guess that yes, it is just a regular center tap transformer. Assuming that's the case:
The outputs will be AC, so -12V doesn't really have any meaning. The 12V here will be 12V AC, and the 24 will be 24V AC.
If you make the center tap 0, then "LABEL 0" will be 12V, and "LABEL 24" will also be 12V (but they will be out of phase with each other).
Based on the labeling, I think it's fairly certain that this is a regular transformer, but I would do some continuity tests just to make sure.
answered Feb 28 at 21:42
DrewDrew
1,9481513
1,9481513
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
add a comment |
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
$begingroup$
Thanks for your answer, As I said above in a comment: 0 and 0 are not connected to each other.. 0 and 12 and 24 are connected on the secondary, 0 and 220 are connected on the primary side. (connected I mean near 0 resistance)
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:51
add a comment |
$begingroup$
0V is arbitrary as it is floating secondary centre-tapped coil.
so you can relabel with 3 choices;
0 : 12Vac : 24Vac
12Vac : 0V : 12Vac +180 deg
24Vac : 12Vac : 0V
$endgroup$
add a comment |
$begingroup$
0V is arbitrary as it is floating secondary centre-tapped coil.
so you can relabel with 3 choices;
0 : 12Vac : 24Vac
12Vac : 0V : 12Vac +180 deg
24Vac : 12Vac : 0V
$endgroup$
add a comment |
$begingroup$
0V is arbitrary as it is floating secondary centre-tapped coil.
so you can relabel with 3 choices;
0 : 12Vac : 24Vac
12Vac : 0V : 12Vac +180 deg
24Vac : 12Vac : 0V
$endgroup$
0V is arbitrary as it is floating secondary centre-tapped coil.
so you can relabel with 3 choices;
0 : 12Vac : 24Vac
12Vac : 0V : 12Vac +180 deg
24Vac : 12Vac : 0V
answered Feb 28 at 22:29
Sunnyskyguy EE75Sunnyskyguy EE75
68.2k22498
68.2k22498
add a comment |
add a comment |
Thanks for contributing an answer to Electrical Engineering Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
Use MathJax to format equations. MathJax reference.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f424940%2fis-that-a-center-tap-tranformer-just-labelled-differently%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
$begingroup$
It's not an autotransformer is it (basically just a big inductor with multiple output taps)? You can check by measuring resistance to see if the 0V and 0V are electrically connected to each other
$endgroup$
– Toor
Feb 28 at 21:41
$begingroup$
@Toor thanks will check, in the mean time their website in french clearly makes a distinction between a regular transformer and autotransformer and the label says "transformer" so I would guess this is not an autotransformer. Getting the multimeter..
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:46
$begingroup$
@Toor Can confirm: 0 and 0 are not connected to each other.. 0 and 12 and 24 are on the secondary, obviously 0 and 220 are on the primary side
$endgroup$
– Mike Gleason jr Couturier
Feb 28 at 21:49
3
$begingroup$
Yeah, so a normal center-tap transformer just labelled specifically for its intended use then.
$endgroup$
– Toor
Feb 28 at 21:59
2
$begingroup$
You can. Just note that one half-winding will be loaded a more than the other half and will affect both voltage outputs.
$endgroup$
– Toor
Feb 28 at 22:06