wiring of occupancy switch in 3-way situation (odd-looking instructions)












2















I'm looking to replace one of the two switches (wired in a standard 3-way configuration) which control an overhead light in a utility room, with an occupancy sensor switch. The room is small enough that the one sensor should provide adequate coverage.



I've purchased an Eaton Model #OS306U, and the wiring instructions look most peculiar to me. The switch has 3 wires, black, red, and blue (plus ground); I'd expect one of the wires to be the "common", and the switch makes a connection between common and either the red or the blue wire, much like a standard mechanical 3-way switch. But it's not wired like that at all. Here is an image from the instructions, for my scenario:



enter image description here



Neutral is wired as normal. The occupancy sensor turns the light on or off by making or breaking the connection between its black and red wires (and the black, being connected to hot, probably powers the logic as well). Meanwhile, the blue wire goes back to the other mechanical switch; this switch either leaves the blue wire open, or shorts it to ground. Apparently the mechanical switch needn't even be a 3-way switch, a single-pole one would be fine (despite the labeling in the drawing).



I can't quite figure out what's going on.










share|improve this question


















  • 1





    But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

    – RustyShackleford
    Feb 10 at 23:20











  • I actually laughed out loud. So true!

    – Harper
    Feb 10 at 23:52






  • 1





    "sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

    – Harper
    Feb 11 at 0:10






  • 1





    Is your ground reliable and genuine?

    – Harper
    Feb 12 at 0:55






  • 1





    So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

    – RustyShackleford
    Feb 12 at 23:43
















2















I'm looking to replace one of the two switches (wired in a standard 3-way configuration) which control an overhead light in a utility room, with an occupancy sensor switch. The room is small enough that the one sensor should provide adequate coverage.



I've purchased an Eaton Model #OS306U, and the wiring instructions look most peculiar to me. The switch has 3 wires, black, red, and blue (plus ground); I'd expect one of the wires to be the "common", and the switch makes a connection between common and either the red or the blue wire, much like a standard mechanical 3-way switch. But it's not wired like that at all. Here is an image from the instructions, for my scenario:



enter image description here



Neutral is wired as normal. The occupancy sensor turns the light on or off by making or breaking the connection between its black and red wires (and the black, being connected to hot, probably powers the logic as well). Meanwhile, the blue wire goes back to the other mechanical switch; this switch either leaves the blue wire open, or shorts it to ground. Apparently the mechanical switch needn't even be a 3-way switch, a single-pole one would be fine (despite the labeling in the drawing).



I can't quite figure out what's going on.










share|improve this question


















  • 1





    But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

    – RustyShackleford
    Feb 10 at 23:20











  • I actually laughed out loud. So true!

    – Harper
    Feb 10 at 23:52






  • 1





    "sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

    – Harper
    Feb 11 at 0:10






  • 1





    Is your ground reliable and genuine?

    – Harper
    Feb 12 at 0:55






  • 1





    So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

    – RustyShackleford
    Feb 12 at 23:43














2












2








2








I'm looking to replace one of the two switches (wired in a standard 3-way configuration) which control an overhead light in a utility room, with an occupancy sensor switch. The room is small enough that the one sensor should provide adequate coverage.



I've purchased an Eaton Model #OS306U, and the wiring instructions look most peculiar to me. The switch has 3 wires, black, red, and blue (plus ground); I'd expect one of the wires to be the "common", and the switch makes a connection between common and either the red or the blue wire, much like a standard mechanical 3-way switch. But it's not wired like that at all. Here is an image from the instructions, for my scenario:



enter image description here



Neutral is wired as normal. The occupancy sensor turns the light on or off by making or breaking the connection between its black and red wires (and the black, being connected to hot, probably powers the logic as well). Meanwhile, the blue wire goes back to the other mechanical switch; this switch either leaves the blue wire open, or shorts it to ground. Apparently the mechanical switch needn't even be a 3-way switch, a single-pole one would be fine (despite the labeling in the drawing).



I can't quite figure out what's going on.










share|improve this question














I'm looking to replace one of the two switches (wired in a standard 3-way configuration) which control an overhead light in a utility room, with an occupancy sensor switch. The room is small enough that the one sensor should provide adequate coverage.



I've purchased an Eaton Model #OS306U, and the wiring instructions look most peculiar to me. The switch has 3 wires, black, red, and blue (plus ground); I'd expect one of the wires to be the "common", and the switch makes a connection between common and either the red or the blue wire, much like a standard mechanical 3-way switch. But it's not wired like that at all. Here is an image from the instructions, for my scenario:



enter image description here



Neutral is wired as normal. The occupancy sensor turns the light on or off by making or breaking the connection between its black and red wires (and the black, being connected to hot, probably powers the logic as well). Meanwhile, the blue wire goes back to the other mechanical switch; this switch either leaves the blue wire open, or shorts it to ground. Apparently the mechanical switch needn't even be a 3-way switch, a single-pole one would be fine (despite the labeling in the drawing).



I can't quite figure out what's going on.







electrical lighting multiway-switch






share|improve this question













share|improve this question











share|improve this question




share|improve this question










asked Feb 10 at 23:20









RustyShacklefordRustyShackleford

168313




168313








  • 1





    But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

    – RustyShackleford
    Feb 10 at 23:20











  • I actually laughed out loud. So true!

    – Harper
    Feb 10 at 23:52






  • 1





    "sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

    – Harper
    Feb 11 at 0:10






  • 1





    Is your ground reliable and genuine?

    – Harper
    Feb 12 at 0:55






  • 1





    So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

    – RustyShackleford
    Feb 12 at 23:43














  • 1





    But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

    – RustyShackleford
    Feb 10 at 23:20











  • I actually laughed out loud. So true!

    – Harper
    Feb 10 at 23:52






  • 1





    "sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

    – Harper
    Feb 11 at 0:10






  • 1





    Is your ground reliable and genuine?

    – Harper
    Feb 12 at 0:55






  • 1





    So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

    – RustyShackleford
    Feb 12 at 23:43








1




1





But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

– RustyShackleford
Feb 10 at 23:20





But if you think about it, you wouldn't want things wired as a normal 3-way. Suppose you walk into the room and turn the light on with the mechanical switch; then once the sensor sees you, it turns the light off.

– RustyShackleford
Feb 10 at 23:20













I actually laughed out loud. So true!

– Harper
Feb 10 at 23:52





I actually laughed out loud. So true!

– Harper
Feb 10 at 23:52




1




1





"sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

– Harper
Feb 11 at 0:10





"sensor sees you and turns the light off"... I see so many attempts to combine different devices with little thought to how they'll interact, and that just sums it up!

– Harper
Feb 11 at 0:10




1




1





Is your ground reliable and genuine?

– Harper
Feb 12 at 0:55





Is your ground reliable and genuine?

– Harper
Feb 12 at 0:55




1




1





So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

– RustyShackleford
Feb 12 at 23:43





So I connected a floor lamp to hot and ground with jumper clips. Lights up fine. Current is about 1/4 amp (had a CFL in it). No noticeable difference in measured voltage with the lamp turned on or off (123.0 on Fluke DVM). Looks like a solid ground and an utterly faulty sensor switch. I exchanged it for a single-pole Lutron I've used in my shipping container that works like a champ; this room is 10x11ft so I think I'll be fine with the occupancy sensor and no second switching location.

– RustyShackleford
Feb 12 at 23:43










2 Answers
2






active

oldest

votes


















2














Yup, I agree with your read. That is exactly what's going on.



I am fairly impressed that UL even allowed this... I seem to recall seeing a bulletin from NFPA to the effect of "alright UL, it's time to stop approving things that use ground for more than ground". Although it may be still allowed since it is surely a millivolt current.



Regardless, it's rather ingenious. It liberates two wires completely, so for instance if the other switch is a remote spur, you can now use black and white for onward power.



Still won't let the put the sensor at the remote spur, that would require 4 wires (line, load, neutral and sense) plus ground.






share|improve this answer
























  • I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

    – RustyShackleford
    Feb 11 at 19:16











  • So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

    – RustyShackleford
    Feb 11 at 19:18











  • Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

    – RustyShackleford
    Feb 11 at 19:24






  • 1





    @RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

    – Harper
    Feb 11 at 20:04








  • 1





    @RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

    – Harper
    Feb 11 at 20:12





















2














I think that you are getting confused by previous experiences with 3-way switches.



The OS306U is an electronic device, much like a light dimmer.



It has a controller that has several inputs, and the output of the controller causes the HOT (black) to be connected to OUTPUT (red); this turns on the light



The controller accepts inputs from three sources.




  1. the push button on the OS306U

  2. the motion sensor on the OS306U

  3. an external switch


All three of these inputs probably connect the associated input pin to ground (same as the remote switch).



The controller is programmed to operate the output in a specific way, dependent on the state of the inputs.






share|improve this answer
























  • Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

    – RustyShackleford
    Feb 11 at 20:04











Your Answer








StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});

function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});


}
});














draft saved

draft discarded


















StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f157275%2fwiring-of-occupancy-switch-in-3-way-situation-odd-looking-instructions%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown

























2 Answers
2






active

oldest

votes








2 Answers
2






active

oldest

votes









active

oldest

votes






active

oldest

votes









2














Yup, I agree with your read. That is exactly what's going on.



I am fairly impressed that UL even allowed this... I seem to recall seeing a bulletin from NFPA to the effect of "alright UL, it's time to stop approving things that use ground for more than ground". Although it may be still allowed since it is surely a millivolt current.



Regardless, it's rather ingenious. It liberates two wires completely, so for instance if the other switch is a remote spur, you can now use black and white for onward power.



Still won't let the put the sensor at the remote spur, that would require 4 wires (line, load, neutral and sense) plus ground.






share|improve this answer
























  • I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

    – RustyShackleford
    Feb 11 at 19:16











  • So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

    – RustyShackleford
    Feb 11 at 19:18











  • Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

    – RustyShackleford
    Feb 11 at 19:24






  • 1





    @RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

    – Harper
    Feb 11 at 20:04








  • 1





    @RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

    – Harper
    Feb 11 at 20:12


















2














Yup, I agree with your read. That is exactly what's going on.



I am fairly impressed that UL even allowed this... I seem to recall seeing a bulletin from NFPA to the effect of "alright UL, it's time to stop approving things that use ground for more than ground". Although it may be still allowed since it is surely a millivolt current.



Regardless, it's rather ingenious. It liberates two wires completely, so for instance if the other switch is a remote spur, you can now use black and white for onward power.



Still won't let the put the sensor at the remote spur, that would require 4 wires (line, load, neutral and sense) plus ground.






share|improve this answer
























  • I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

    – RustyShackleford
    Feb 11 at 19:16











  • So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

    – RustyShackleford
    Feb 11 at 19:18











  • Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

    – RustyShackleford
    Feb 11 at 19:24






  • 1





    @RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

    – Harper
    Feb 11 at 20:04








  • 1





    @RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

    – Harper
    Feb 11 at 20:12
















2












2








2







Yup, I agree with your read. That is exactly what's going on.



I am fairly impressed that UL even allowed this... I seem to recall seeing a bulletin from NFPA to the effect of "alright UL, it's time to stop approving things that use ground for more than ground". Although it may be still allowed since it is surely a millivolt current.



Regardless, it's rather ingenious. It liberates two wires completely, so for instance if the other switch is a remote spur, you can now use black and white for onward power.



Still won't let the put the sensor at the remote spur, that would require 4 wires (line, load, neutral and sense) plus ground.






share|improve this answer













Yup, I agree with your read. That is exactly what's going on.



I am fairly impressed that UL even allowed this... I seem to recall seeing a bulletin from NFPA to the effect of "alright UL, it's time to stop approving things that use ground for more than ground". Although it may be still allowed since it is surely a millivolt current.



Regardless, it's rather ingenious. It liberates two wires completely, so for instance if the other switch is a remote spur, you can now use black and white for onward power.



Still won't let the put the sensor at the remote spur, that would require 4 wires (line, load, neutral and sense) plus ground.







share|improve this answer












share|improve this answer



share|improve this answer










answered Feb 11 at 0:05









HarperHarper

70.6k447142




70.6k447142













  • I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

    – RustyShackleford
    Feb 11 at 19:16











  • So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

    – RustyShackleford
    Feb 11 at 19:18











  • Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

    – RustyShackleford
    Feb 11 at 19:24






  • 1





    @RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

    – Harper
    Feb 11 at 20:04








  • 1





    @RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

    – Harper
    Feb 11 at 20:12





















  • I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

    – RustyShackleford
    Feb 11 at 19:16











  • So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

    – RustyShackleford
    Feb 11 at 19:18











  • Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

    – RustyShackleford
    Feb 11 at 19:24






  • 1





    @RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

    – Harper
    Feb 11 at 20:04








  • 1





    @RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

    – Harper
    Feb 11 at 20:12



















I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

– RustyShackleford
Feb 11 at 19:16





I still don't understand exactly what's going on. Flipping the mechanical switch changes the blue wire from "open" to "shorted to ground", or vice versa. So if the light is off, flipping the mechanical switch turns it on, and the sensor goes into its "wait for no motion sensed for specified period of time" state. If the light is on, flipping the mechanical switch turns it off; so the sensor needs to ignore sensed motion for some time after that (otherwise we have the amusing situation I meant to describe in my 1st comment on OP).

– RustyShackleford
Feb 11 at 19:16













So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

– RustyShackleford
Feb 11 at 19:18





So there's a kind of state machine in the smart switch, that knows when the blue wire's connectivity has changed, in either direction.

– RustyShackleford
Feb 11 at 19:18













Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

– RustyShackleford
Feb 11 at 19:24





Haven't installed it yet. Trying to understand theory of operation; that was meant to be my original question.

– RustyShackleford
Feb 11 at 19:24




1




1





@RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

– Harper
Feb 11 at 20:04







@RustyShackleford I would bet the engineers thought seriously about UX and chose that which would be least likely to cause WTF returns from customers. At least, if the device has a manual button, I would expect the remote switch to do the same thing as the button.

– Harper
Feb 11 at 20:04






1




1





@RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

– Harper
Feb 11 at 20:12







@RustyShackleford After much observation and contemplation of this question over the years, I conclude the likeliest answer is 42.

– Harper
Feb 11 at 20:12















2














I think that you are getting confused by previous experiences with 3-way switches.



The OS306U is an electronic device, much like a light dimmer.



It has a controller that has several inputs, and the output of the controller causes the HOT (black) to be connected to OUTPUT (red); this turns on the light



The controller accepts inputs from three sources.




  1. the push button on the OS306U

  2. the motion sensor on the OS306U

  3. an external switch


All three of these inputs probably connect the associated input pin to ground (same as the remote switch).



The controller is programmed to operate the output in a specific way, dependent on the state of the inputs.






share|improve this answer
























  • Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

    – RustyShackleford
    Feb 11 at 20:04
















2














I think that you are getting confused by previous experiences with 3-way switches.



The OS306U is an electronic device, much like a light dimmer.



It has a controller that has several inputs, and the output of the controller causes the HOT (black) to be connected to OUTPUT (red); this turns on the light



The controller accepts inputs from three sources.




  1. the push button on the OS306U

  2. the motion sensor on the OS306U

  3. an external switch


All three of these inputs probably connect the associated input pin to ground (same as the remote switch).



The controller is programmed to operate the output in a specific way, dependent on the state of the inputs.






share|improve this answer
























  • Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

    – RustyShackleford
    Feb 11 at 20:04














2












2








2







I think that you are getting confused by previous experiences with 3-way switches.



The OS306U is an electronic device, much like a light dimmer.



It has a controller that has several inputs, and the output of the controller causes the HOT (black) to be connected to OUTPUT (red); this turns on the light



The controller accepts inputs from three sources.




  1. the push button on the OS306U

  2. the motion sensor on the OS306U

  3. an external switch


All three of these inputs probably connect the associated input pin to ground (same as the remote switch).



The controller is programmed to operate the output in a specific way, dependent on the state of the inputs.






share|improve this answer













I think that you are getting confused by previous experiences with 3-way switches.



The OS306U is an electronic device, much like a light dimmer.



It has a controller that has several inputs, and the output of the controller causes the HOT (black) to be connected to OUTPUT (red); this turns on the light



The controller accepts inputs from three sources.




  1. the push button on the OS306U

  2. the motion sensor on the OS306U

  3. an external switch


All three of these inputs probably connect the associated input pin to ground (same as the remote switch).



The controller is programmed to operate the output in a specific way, dependent on the state of the inputs.







share|improve this answer












share|improve this answer



share|improve this answer










answered Feb 11 at 19:49









jsotolajsotola

86828




86828













  • Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

    – RustyShackleford
    Feb 11 at 20:04



















  • Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

    – RustyShackleford
    Feb 11 at 20:04

















Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

– RustyShackleford
Feb 11 at 20:04





Yep. There's a finite-state machine (FSM) in the controller. Hopefully it'll do what I want it too.

– RustyShackleford
Feb 11 at 20:04


















draft saved

draft discarded




















































Thanks for contributing an answer to Home Improvement Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid



  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.


To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f157275%2fwiring-of-occupancy-switch-in-3-way-situation-odd-looking-instructions%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







Popular posts from this blog

How to change which sound is reproduced for terminal bell?

Can I use Tabulator js library in my java Spring + Thymeleaf project?

Title Spacing in Bjornstrup Chapter, Removing Chapter Number From Contents